perature alarm will acvate at 9°C = (4 [setpoint] + 3 [Ahi] + 2
[hysteresis])
The
number of degrees C colder relave to setpoint
that will iniate a low temperature alarm. Once
the compartment temperature exceeds the low temperature
alarm value, the control will delay AdL minutes before iniang
the alarm. See Alarm Delay secon below for instrucons to
set alarm delay. While ALo is displayed on the screen, press and
hold SET key to view the value of ALohi. To adjust the value, con-
nue to hold SET then use the WARMER and COLDER keys unl
the desired value is shown on the screen. Release the SET key to
conrm the new seng. Factory default value for ALo is -2.0°C.
Note: Seng ALo = 0 will disable the low temperature alarm.
No hysteresis value is added to ALo. For example, let setpoint =
4°C, and ALo = -3. The low temperature alarm will acvates at
1°C = (4 [setpoint] + -3 [ALo])
The number of minutes the
compartment temperature must be outside the
range specied by Ahi and ALo before a tempera-
ture alarm acvates. While AdL is shown on the screen, press
and hold SET key to view the value of AdL. To adjust the value,
connue to hold SET then use the WARMER and COLDER keys
unl the desired value is shown on the screen. Release SET key
to conrm the new seng. Factory default value for AdL is 60
minutes.

 The operang me of
the condenser since the last cleaning. The control
monitors the operang me of the condenser fan to determine
when the condenser is in need of being cleaned. While cnd is
displayed on the screen, press and hold SET key to view the value
of cnd. The value shown is the number of weeks the condenser
has been operang. To reset cnd, connue to hold the SET key
then press and release the ON/OFF key.
When the control recommends the condenser be cleaned, a
reminder will be displayed on the screen (see Alarm Codes.) To
clear the alarm code, reset the value in cnd following the instruc-
ons printed above.
 This feature is
used to prevent incidental changes to the set
point, or accidentally turning the unit o. While
Loc is displayed on the screen, press and hold the SET key. If
“No” is displayed, Lockout feature is o, and all keys
are enabled. If “Yes” is displayed, Lockout feature is
ON. The ability to turn the unit on and o, as well as the ability
to adjust setpoint will be disabled. To change the keypad lockout
seng, connue to hold the SET key, then use the WARMER and
COLDER keys to set the desired value.
APPENDIX A, ADDITIONAL MICROSENTRY FEATURES

To access the informaon menu, press the SET key, and immedi-
ately release it.
In the informaon menu, a 2 or 3 digit code will be displayed
represenng each entry in the informaon menu. The rst code
displayed will be t1. With each sequenal press and release of
the SET key, the following codes will appear in this order: t1, thi,
tLo, Ahi, ALo, AdL, cnd, and Loc.
To view the value of each code, press and hold the SET key aer
the desired code is displayed. Addionally, the WARMER and
COLDER keys may be used to scroll through the menu. To exit
the informaon menu, press the ON/OFF key, or wait for several
seconds with no key presses.
 Press and
hold the “SET” key to display the current interior
temperature.
 While
thi is shown on the screen, press and hold the
“SET” key to display the maximum recorded
temperature. The temperature is updated every 5 minutes. To
reset the maximum temperature; connue to hold the SET key,
then press and release the ON/OFF key to reset the maximum
temperature. The maximum temperature will be reset to the
current compartment temperature.
It is recommended that thi be reset aer the inial pull-down
(24 hours aer power on) to clear any residual values.
While tLo
is shown on the screen, press and hold the “SET
key to display the minimum recorded tempera-
ture. The temperature is updated every 5 minutes. Connue to
hold the SET key then, press and release the ON/OFF key to reset
the minimum temperature. The minimum temperature will
be reset to the current compartment temperature. It is recom-
mended that tLo be reset aer the inial pull down (24 hours
aer power on) to clear any residual values.
The
number of degrees C warmer relave to the
setpoint that will iniate a high temperature
alarm. Once the compartment temperature exceeds the high
temperature alarm value, the control will delay AdL minutes
before iniang the alarm. See Alarm Delay secon below for
instrucons to set alarm delay. While Ahi is displayed on the
screen, press and hold SET key to view the value of Ahi. To
adjust the value, connue to hold SET then use the WARMER
and COLDER keys unl the desired value is shown on the screen.
Release the SET key to conrm the new seng. Factory default
value for Ahi is 2.0°C.
Note: Seng Ahi = 0 will disable the high temperature alarm.
The control’s 2°C Hysteresis value is automacally added to Ahi.
For example, let setpoint = 4°C, and Ahi = 3. The high tem-
15