perature alarm will acvate at 9°C = (4 [setpoint] + 3 [Ahi] + 2
[hysteresis])
The
number of degrees C colder relave to setpoint
that will iniate a low temperature alarm. Once
the compartment temperature exceeds the low temperature
alarm value, the control will delay AdL minutes before iniang
the alarm. See Alarm Delay secon below for instrucons to
set alarm delay. While ALo is displayed on the screen, press and
hold SET key to view the value of ALohi. To adjust the value, con-
nue to hold SET then use the WARMER and COLDER keys unl
the desired value is shown on the screen. Release the SET key to
conrm the new seng. Factory default value for ALo is -2.0°C.
Note: Seng ALo = 0 will disable the low temperature alarm.
No hysteresis value is added to ALo. For example, let setpoint =
4°C, and ALo = -3. The low temperature alarm will acvates at
1°C = (4 [setpoint] + -3 [ALo])
The number of minutes the
compartment temperature must be outside the
range specied by Ahi and ALo before a tempera-
ture alarm acvates. While AdL is shown on the screen, press
and hold SET key to view the value of AdL. To adjust the value,
connue to hold SET then use the WARMER and COLDER keys
unl the desired value is shown on the screen. Release SET key
to conrm the new seng. Factory default value for AdL is 60
minutes.
The operang me of
the condenser since the last cleaning. The control
monitors the operang me of the condenser fan to determine
when the condenser is in need of being cleaned. While cnd is
displayed on the screen, press and hold SET key to view the value
of cnd. The value shown is the number of weeks the condenser
has been operang. To reset cnd, connue to hold the SET key
then press and release the ON/OFF key.
When the control recommends the condenser be cleaned, a
reminder will be displayed on the screen (see Alarm Codes.) To
clear the alarm code, reset the value in cnd following the instruc-
ons printed above.
This feature is
used to prevent incidental changes to the set
point, or accidentally turning the unit o. While
Loc is displayed on the screen, press and hold the SET key. If
“No” is displayed, Lockout feature is o, and all keys
are enabled. If “Yes” is displayed, Lockout feature is
ON. The ability to turn the unit on and o, as well as the ability
to adjust setpoint will be disabled. To change the keypad lockout
seng, connue to hold the SET key, then use the WARMER and
COLDER keys to set the desired value.
APPENDIX A, ADDITIONAL MICROSENTRY™ FEATURES
To access the informaon menu, press the SET key, and immedi-
ately release it.
In the informaon menu, a 2 or 3 digit code will be displayed
represenng each entry in the informaon menu. The rst code
displayed will be t1. With each sequenal press and release of
the SET key, the following codes will appear in this order: t1, thi,
tLo, Ahi, ALo, AdL, cnd, and Loc.
To view the value of each code, press and hold the SET key aer
the desired code is displayed. Addionally, the WARMER and
COLDER keys may be used to scroll through the menu. To exit
the informaon menu, press the ON/OFF key, or wait for several
seconds with no key presses.
Press and
hold the “SET” key to display the current interior
temperature.
While
thi is shown on the screen, press and hold the
“SET” key to display the maximum recorded
temperature. The temperature is updated every 5 minutes. To
reset the maximum temperature; connue to hold the SET key,
then press and release the ON/OFF key to reset the maximum
temperature. The maximum temperature will be reset to the
current compartment temperature.
It is recommended that thi be reset aer the inial pull-down
(24 hours aer power on) to clear any residual values.
While tLo
is shown on the screen, press and hold the “SET”
key to display the minimum recorded tempera-
ture. The temperature is updated every 5 minutes. Connue to
hold the SET key then, press and release the ON/OFF key to reset
the minimum temperature. The minimum temperature will
be reset to the current compartment temperature. It is recom-
mended that tLo be reset aer the inial pull down (24 hours
aer power on) to clear any residual values.
The
number of degrees C warmer relave to the
setpoint that will iniate a high temperature
alarm. Once the compartment temperature exceeds the high
temperature alarm value, the control will delay AdL minutes
before iniang the alarm. See Alarm Delay secon below for
instrucons to set alarm delay. While Ahi is displayed on the
screen, press and hold SET key to view the value of Ahi. To
adjust the value, connue to hold SET then use the WARMER
and COLDER keys unl the desired value is shown on the screen.
Release the SET key to conrm the new seng. Factory default
value for Ahi is 2.0°C.
Note: Seng Ahi = 0 will disable the high temperature alarm.
The control’s 2°C Hysteresis value is automacally added to Ahi.
For example, let setpoint = 4°C, and Ahi = 3. The high tem-
15